Installation guide

1–Installation
Planning the Installation
1-4 D000102-000 B
Figure 1-2 Fiber Optic Bend Radius
Uninterruptible Power Supply
Consider the following when selecting Uninterruptible Power Supply (UPS)
equipment:
The minimum amperage requirements for a UPS:
Calculate VA (Volt-Amps): Locate the voltage and amperage requirements
for each piece of equipment (usually located on a sticker on the back or bottom
of the equipment). Multiply the numbers together to get VA.
Add the VA from each piece of equipment together to find the total VA
requirement. Then add 30% to determine the minimum amperage
requirements for the UPS.
Transition time (the time necessary for the UPS to transfer from utility power to
full-load battery power).
The longest potential time period the UPS might be required to supply backup
power.
Whether or not the UPS unit also provides online protection.
Table 1-2. IB Fiber Optic Cable Guidelines
IB Fiber Optic Cable Bend Radii
Cable Type Bend Radius
Fiber Optic Standard Cable 25 millimeters
NOTE: A 50mm diameter is the smallest circle limit