Specifications

40 Sun StorageTek 6140 Array Release Notes November 2008
Caution A qualified service person is required to make the DC power connection
per NEC and CEC guidelines. A two-pole 20-amp circuit breaker is required
between the DC power source and the array module for over-current and short-
circuit protection. Before turning off any power switches on a DC-powered module,
you must disconnect the two-pole 20-amp circuit breaker.
Caution Electrical grounding hazard This equipment is designed to permit the
connection of the D.C. supply circuit to the earthing conductor at the equipment.
FIGURE B-1 shows the DC Power Connectors and DC Power Switch.
FIGURE B-1 DC Power Connectors and DC Power Switch.
Caution Risk of electrical shock This unit has more than one power source.
To remove all power from the unit, all DC MAINS must be disconnected by
removing all power connectors (item 4 in Appendix FIGURE B-2) from the power
supplies.