Use and Care Guide

4. The electrical supply for the spa must include a suitable rated
switch or circuit breaker to open all ungrounded supply conduc-
tors to comply with Section 422-20 of the National Electric
Code, ANSI/NFPA 70. The disconnecting means must be readi-
ly accessible to the spa’s occupant but installed at least 10 feet
from the spa water. Check with local municipalities for addi-
tional code requirements.
5. The electrical circuit for the spa must include a suitable
ground fault circuit interrupter (GFCI) as required by NEC Article
680-42. Your spa requires a Neutrally Protected (GFCI) Ground
Fault Circuit Interrupter, see the illustration on the following
page for the proper wiring for your spa’s GFCI.
15