Installation manual
PCX 256 PROGRAMMING MANUAL
RINS868-6 Page: 41
5.15.2 STU / ATE Pin Outputs (Defaults)
Any communicating device with the industry standard footprint may be plugged onto the control
panel STU / ATE (Alarm Transmission Equipment) pins. The default types for the footprint are as
follows:
COM LOOM Default Type PGM Number
1 (Blue)
Fire 0001
2 (Orange)
HU Device Any 0009
3 (Yellow)
Unconfirmed Any 0018
4 (Brown)
Final Arm Any 0022
5 (Purple)
Tamper Any 0007
6 (Green)
Confirmed Any 0006
7 (Black)
Omit Rearm Any 0017
8 (Purple)
AC Fail 0052
9 (White)
Global Fault 2 0056
10 (Light Grey)
Test ATS 0064
NOTE: There is an “Invert ATE outputs” option for use with positive removed signalling.
Insufficient current is available for any other application. Please see ‘Site Options, page 47.
These are programmed in ‘Change Outputs’ under ‘Endstation PGMs’.
For programming of the onboard Digi channels please see page: 58.
5.15.3 PCX-PROX/EXT PGM Output
The RED LED on the PCX-PROX/EXT can be programmed so that it follows an output.
To achieve this, go to ‘CHANGE OUTPUTS’ and then ‘Reader PGMs’ and program the first PGM
output (PGM1) to whichever type is required.
For example you may want the Prox to show the system armed, therefore you can use the output
“0204: Final Arm A”. The RED LED will then be illuminated once Partition A has armed.
Visual Keypad Programming Procedure
CHANGE OUTPUTS
Change Outputs
Using the and keys, scroll to ‘CHANGE
OUTPUTS?’ Press the key
Endstation PGMs
To program the control panel PGMs and the
STU/ATE pins press the key.