Specifications
14 15
RDOC 279 issue 2
9 PROGRAMMING
then
then or to display E
Zone Number
or A
or i
or o
Press when required Zon type
is displayed. Repeat sequence for
every zone on each set mode
9.1 FACTORY DEFAULTS
The panel is now programmed to its factory settings as shown below.
Master User code : 1234 (0000-9999)
Limited User code : 5678 (0000-9999)
Engineer code : 9999 (0000-9999)
Bell timer : 20 minutes (programable 2 to 20 mins)
Entry/exit time : 30 seconds (programable 2 to 255 secs)
Event log : Engineer reset of log
The following key applies to the table below:
E = Entry/exit zone
A = Access zone
i = Immediate zone
o = Omitted zone (not active)
Zone number
123456
Full set E A i i i i
Part set 1 EAiiii
Part set 2 EAiiii
Part set 3 E A i i i i
9.2 Entering Engineer Mode
Key
The fault LED will flash when the Paragon Super is in Engineer mode.
The day LED will flash during programming of any of the functions.
Whilst in Engineer mode, you are able to remove any covers without creating a tamper
alarm.
9.3 Setting Part-Set Volume Control
The Paragon Super has been designed with a unique feature enabling the customer to
have a reduced volume tone on part-setting of the control panel.
This volume is controlled via the adjustable volume pot on the main processor board.
1. Remove lid.
2. Set volume pot to desired volume
3.Depressed a number key to check desired volume has been reached.
4.Replace cover.
This volume control can be overridden for full setting purposes by simply pressing in the
4 digit Master or Limited User code. THe above only applies, when extension speakers
are being used. Each RKP has its own volume control pot.
9.4 Resetting the Non Volatile Memory (NVM) to Factory Settings
The NVM will reset itself to the factory settings if the reset pins on the PCB are
shorted together on power up. This also requires the back up battery to be
disconected. For normal operation the jumper should be removed from two pins.
9.5 Setting the panel when mains fails
Under normal operation the panel will indicate a fault condition if the mains supply is
disconnected. In this state the panel cannot be set. This feature can be overridden by
shorting together (with the jumper supplied) the mains fail disable pins on the PCB.
9.6 Programming Set Modes.
Any zone may be programmed to be any one of the following:
Entry / Exit = E Access = A
Immediate = I Omitted = O
To program the zones for the 4 set modes, the following key sequence should be used.
FULL SET Key
PART SET 1 Key
PART SET 2 Key
PART SET 3 Key
Should you wish to view any zone status within a Set mode use the same procedure, but
do not scroll the keys. Press to exit.
9.7 Setting the Alarm Bell Time
To adjust the alarm bell cut off time press
followed by the required time in minutes ( to minutes)
followed by .
Incorrect entry gives an audible error tone and correct entry gives three bleeps.
The alarm bell cut off time for the Paragon Super is factory set to 20 minutes.
9.8 Setting Entry / Exit Time
To set the required time for Entry / Exit time, press
followed by the time required in seconds ( to seconds) followed by .
Incorrect entry gives an audible error tone and correct entry gives three bleeps.
The Entry / Exit time is factory set to 30 seconds.
9.9 Changing the Engineer Code
Enter
then the old Engineer Code (Factory Set at 9999)
- gives an audible acceptance tone