User guide
T82 Technical data
33
12 Technical data
12.1 Input
Measured variable Temperature (temperature-linear transmission behavior), resistance and voltage.
Type of input Two independent sensors can be connected. The measuring inputs are not galvanically isolated
from each other.
Type of input Designation Measuring range limits
Resistance thermometer (RTD)
as per IEC 60751:2008
(a = 0.003851)
Pt100
Pt200
Pt500
Pt1000
–200 to +850 °C (–328 to +1 562 °F)
–200 to +850 °C (–328 to +1 562 °F)
–200 to +500 °C (–328 to +932 °F)
–200 to +250 °C (–328 to +482 °F)
as per JIS C1604:1984
(a = 0.003916)
Pt100 –200 to +510 °C (–328 to +950 °F)
as per DIN 43760 IPTS-68
(a = 0.006180)
Ni100
Ni120
–60 to +250 °C (–76 to +482 °F)
–60 to +250 °C (–76 to +482 °F)
as per GOST 6651-94
(a = 0.003910) (for Cu: a = 0.004280)
Pt100
Pt50
Cu50
–200 to +850 °C (–328 to +1 562 °F)
–185 to +1 100 °C (–301 to +2 012 °F)
–175 to +200 °C (–283 to +392 °F)
as per OIML R84: 2003
and GOST 6651-94 (a = 0.006170) (for
Cu: a = 0.004260)
Cu50
Ni100
Ni120
–50 to +200 °C (–58 to +392 °F)
–60 to +180 °C (–76 to +356 °F)
–60 to +180 °C (–76 to +356 °F)
as per OIML R84: 2003 (a = 0.004280)
Cu50 –180 to +200 °C (–292 to +392 °F)
Pt100 (Callendar van
Dusen)
Nickel polynomial
Copper polynomial
The measuring range limits are specified by entering the limit values that depend on the
coefficients A to C and R0.
•
Type of connection: 2-wire, 3-wire or 4-wire connection, sensor current: £ 0.3 mA
•
With 2-wire circuit, compensation of wire resistance possible (0 to 30 W)
•
With 3-wire and 4-wire connection, sensor wire resistance to max. 50 W per wire
Resistance transmitter
Resistance W 10 to 400 W
10 to 2 000 W
Thermocouples (TC)
to IEC 584 part 1
Type B (PtRh30-PtRh6)
Type E (NiCr-CuNi)
Type J (Fe-CuNi)
Type K (NiCr-Ni)
Type N (NiCrSi-NiSi)
Type R (PtRh13-Pt)
Type S (PtRh10-Pt)
Type T (Cu-CuNi)
+40 to +1 820 °C (+104 to +3 308 °F)
–270 to +1 000 °C (–454 to +1 832 °F)
–210 to +1 200 °C (–346 to +2 192 °F)
–270 to +1 372 °C (–454 to +2 501 °F)
–270 to +1 300 °C (–454 to +2 372 °F)
–50 to +1 768 °C (–58 to +3 214 °F)
–50 to +1 768 °C (–58 to +3 214 °F)
–260 to +400 °C (–436 to +752 °F)
Recommended temperature range:
+100 to +1 500 °C (+212 to +2 732 °F)
0 to +750 °C (+32 to +1 382 °F)
+20 to +700 °C (+68 to +1 292 °F)
0 to +100 °C (+32 to +2 012 °F)
0 to +100 °C (+32 to +2 012 °F)
0 to +1 400 °C (+32 to +2 552 °F)
0 to +1 400 °C (+32 to +2 552 °F)
–185 to +350 °C (–301 to +662 °F)
to ASTM E988 Type C (W5Re-W26Re)
Type D (W3Re-W25Re)
0 to +2 315 °C (+32 to +4 199 °F)
0 to +2 315 °C (+32 to +4 199 °F)
0 to +2 000 °C (+32 to +3 632 °F)
0 to +2 000 °C (+32 to +3 632 °F)
to DIN 43710 Type L (Fe-CuNi)
Type U (Cu-CuNi)
–200 to +900 °C (–328 to +1 652 °F)
–200 to +600 °C (–328 to +1 112 °F)
0 to +700 °C (+32 to +1 292 °F)
–185 to +400 °C (–301 to +752 °F)
• Internal cold junction (Pt100)
• External cold junction: configurable value –40 to +85 °C (–40 to +185 °F)
•
Max. sensor resistance 10 kW (if sensor resistance is greater than 10 kW, error message as per NAMUR NE89)
Voltage transmitter (mV)
Millivolt transmitter (mV) –20 to 100 mV