User guide
T82
Integrating the transmitter via the HART
®
protocol
23
7
Integrating the transmitter via the HART
®
protocol
Version data for the device
Firmware Version 01.00.zz • On the title page of the Operating instructions
• On the nameplate
• Parameter firmware version
Diagnostics ® Device info® Firmware version
Manufacturer ID 00b5 Manufacturer ID parameter
Diagnostics ® Device info® Manufacturer ID
Device type ID 0081 Device type parameter
Diagnostics ® Device info ® Device type
HART protocol revision 6.0 ---
Device revision 1 • On the transmitter nameplate
• Device revision parameter
Diagnostics ® Device info ® Device revision
The following is a list of the suitable device description (DD) file for each individual operating tool
with information on the source.
Operating tools
Operating tool
Sources for obtaining device descriptions (DD)
FieldCare
(Endress+Hauser)
www.endress.com ® Download Area
AMS Device Manager
(Emerson Process Management)
Internet-download on the manufacturer's website
Field Communicator 375, 475
(Emerson Process Management)
Use update function of handheld terminal
7.1 HART device variables and measured values
The following measured values are assigned to the device variables at the factory:
Device variables for temperature measurement
Device variable
Measured value
Primary device variable (PV) Sensor 1
Secondary device variable (SV) Device temperature
Tertiary device variable (TV) Sensor 1
Quaternary device variable (QV) Sensor 1
It is possible to change the assignment of device variables to process variables in the Expert
® Communication ® HART output menu.
7.2 Device variables and measured values
The following measured values are assigned to the individual device variables:
Device variable code
Measured value
0 Sensor 1
1 Sensor 2