Owner manual
Series 642 Commissioning
Pyromation, Inc. 25
Function group SERVICE FUNCTIONS
Availability in TransComm Light, HART
®
communicator DXR375 (symbol
7
) TransComm Light
7
Security locking Set-up release code.
Input:
• Lock = 0
•Release = 246
++
Reset to default Reset to factory default values.
Input: 642
0
++
Output simulation Activate simulation mode.
Input:
• OFF
•ON
++
Simulation value Input of the simulation value (current).
Input: 3.58 to 23 mA
++
User calibration
(trim) analog output
For changing the 4 or 20 mA value by ± 0.150 mA
• Trimming 4 mA
• Trimming 20 mA
++
Function group MEASURED VALUES
Availability in TransComm Light, HART
®
communicator DXR375 (symbol
7
)TransComm Light
7
PV PV value ++
AO PV value in mA - +
PV % PV value in % - +
Sensor Sensor process value - +
Internal temperature Internal temperature of the device - +