Owner manual

Series 642 Commissioning
Pyromation, Inc. 19
6.4 Device configuration
6.4.1 Description of device functions
All parameters that can be read out and set-up for the configuration of the temperature transmitter
are listed and described in the following tables. The menu structure in the PC configuration software
TransComm Light and in the HART
®
communicator DXR375 are shown in the following tables.
Factory default setup is shown in bold text.
Function group STANDARD SETTINGS
Availability in TransComm Light, HART
®
communicator DXR375 (symbol
7
) TransComm Light
7
PV unit Enter the unit of the PV (= Primary Value)
Input: ° C, °F, K, R, mV or Ω
The setting PV unit has priority, the selection list of the sensor type is shown
independently from the PV unit.
++
Function group SENSOR
Availability in TransComm Light, HART
®
communicator DXR375 (symbol
7
) TransComm Light
7
Sensor type
IEC 60751
JIS
IEC 60751
Edison Copper
Winding No. 15
SAMA
Edison Curve No. 7
GOST
Sensor type
Pt100
Pt200
Pt100
Pt500
Pt1000
Ni100
Ni1000
Cu10
Pt100
Ni120
Pt50
Pt100
Cu50
Cu100
Polynomial RTD
Callendar - van
Dusen (Pt100)
Meas. range
start
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-60 °C (-76 °F)
-60 °C (-76 °F)
-100 °C (-148 °F)
-100 °C (-148 °F)
-70 °C (-94 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
-200 °C (-328 °F)
Meas. range
full scale value
850 °C (1562 °F)
850 °C (1562 °F)
649 °C (1200.2 °F)
250 °C (482 °F)
250 °C (482 °F)
250 °C (482 °F)
150 °C (302 °F)
260 °C (500 °F)
700 °C (1292 °F)
270 °C (518 °F)
1100 °C (2012 °F)
850 °C (1562 °F)
200 °C (392 °F)
200 °C (392 °F)
850 °C (1562 °F)
850 °C (1562 °F)
min. range
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
10 K (18 °F)
++