Operating instructions
Stove Vent Pipe/ln ta ke Installa tion 
IT IS RECOMMENDED THAT ONLY AN AUTHORIZED DEALER  INSTALL 
YOUR PELLET STOVE.  THE FOLLOWING INSTALLATION GUIDELINES 
MUST BE  FOLLOWED TO ENSURE CONFORMITY WITH BOTH THE SAFETY 
LISTING OF THE STOVE AND LOCAL BUILDING CODES. 
General guidelines for installing the exhaust system: 
A 
3 or 4  inch listed type 
"L" 
pellet vent exhaust system must be used for freestanding installations and 
attached (and sealed) to the pipe connector provided on the back of the stove.  Use a 3-to-4 inch adapter or 
a 3-to-4 inch Tee in order to run 
4 
inch pipe. 
The vent termination must be located no less than 
48" 
(1.2114  from any opening through which flue gases 
could re-enter the building, 
(i.e.  windows and doors) not less than 
24" 
(.6m) from an adjacent building, 
and not less than 
7' 
(2.2m) above grade when located near  public walkways. The final termination of the 
exhaust system must be configured so that flue gases do not jeopardize the safety of people passing by, 
overheat combustible portions of nearby structures or enter the building. Keep brush,  plants and shrubs at 
least 36" 
(.9m) away from vent termination.  Since sparks may escape from the exhaust pipe of any stove, 
always use caution when positioning the vent pipe. (Refer to pipe manufacturer's instructions when 
installing and terminating the exhaust.) 
Ninety-degree elbows accumulate fly ash and soot which reduces the exhaust flow and performance of the 
stove. Horizontal runs of pipe will collect fly ash as  well.  It 
is 
recornmended that a single or double clean- 
out 'tee'  be installed at every 90 degree turn so that fly ash can accumulate at the bottom of the 'tee'.  If a 
90 degree turn connects a vertical  run of pipe to a horizontal run (as you follow the exhaust away from the 
stove), a tee 
is 
not required. At any other 90 degree turn,  installation of a clean-out tee is recommended to 
permit periodic cleaning of both the horizontal and vertical  runs of pipe. 
Total length of horizontal vent must not exceed 
25ft. (7.7m).  See  page 17 
CAUTION: 
On 
all direct vent installations (short, horizontal runs); care should be taken when choosing 
a location for terminating the vent. 
(It 
is 
NOT 
recommended to directly vent the exhaust on the prevail- 
ing wind side of the house). 
"DO NOT INSTALL A FLUE  DAMPER IN THE EXHAUST  VENTING SYSTEM  OF THlS UNIT". 
"DO NOT CONNECT 
THlS TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE". 
FIREPLACE INSERT: 
A 
3" 
single-wall, stainless steel flexible or rigid exhaust pipe may 
be 
used for insert installations and must 
be attached to the stainless steel exhaust tee provided with each insert model stove. 
When venting into an existing chimney (masonry or factory built) thechimney must be cleaned,  with all 
creosote,  dust and ashes removed. 
The 
"L" 
vent or single wall stainless exhaust system must be installed so as  to 
be 
GAS TIGHT! The vent 
manufacturer's  installation procedures must be followed.  In addition, pipe connections, joints and all pipe 
seams within the home should be sealed with room temperature vulcanizing, high temperature 
silicone sealer 
(RTV). 
If an insert 
is 
to be installed into an unlined masonry chimney,  3" or 
4" 
rigid or flex pipe must be extended 
to the top of the existing chimney. The top of the existing chimney should be sealed with a metal plate after 
the pellet vent has been installed. 










