User manual
Modbus/TCP 7-8
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Status Data Table
The status data table is a collection of status and diagnostic information for the
BridgeWay DeviceNet interface. The information in the table is updated approxi-
mately once a second.
Modbus
Input
Register
Size
in
Words
Data Type Name Description
257 2 UDINT Scan Counter The number of DeviceNet I/O scans
that have taken place since the Bridge-
Way was powered up.
259 4 64-bit Bit-
string
Faulted Node
Table
Indicates which DeviceNet slaves are
faulted.
Each bit represents the status of the
slave at the corresponding MAC ID.
263 4 64-bit Bit-
string
Auto Verify Error
Table
Indicates which DeviceNet slaves are
the incorrect device type.
Each bit represents the status of the
slave at the corresponding MAC ID.
267 4 64-bit Bit-
string
Idle Node Table Indicates which DeviceNet slaves are
in Idle mode.
Each bit represents the status of the
slave at the corresponding MAC ID.
271 4 64-bit Bit-
string
Active Node
Table
Indicates which DeviceNet nodes are
configured in the BridgeWay’s scan
list. Each bit represents a device at the
corresponding MAC ID. If the bit is
set, that device is being actively
scanned by the BridgeWay’s
DeviceNet master.
275 2 ASCII[4] Status Display Mimics a 4-character alpha-numeric
display.
If there are no faults, the display indi-
cates the BridgeWay MAC ID and its
Run/Idle status.
If there are faults, the display will
scroll through the MAC IDs of the
faulted nodes and display the error
code associated with each. See
Table 10-6, “Node Status Codes,” on
page 6 for a list of error codes.
Table 7-11 Status Data Format