EtherNet/IP 6-6
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Output Assembly
The output assembly contains a 32-bit command register followed by the
DeviceNet slave output data.
The DeviceNet slave output data format and content is determined by the
DeviceNet scanner configuration. The DeviceNet slave data appears in the table
as it is mapped to the DeviceNet output connections. The DeviceNet slave output
data in the assembly is 492 bytes long; however, only the size configured for the
output data will be used, the remaining space will be ignored.
Note: EtherNet/IP I/O connections append a 32-bit Run/Idle register at the front
of the output data. The actual output data transferred in the I/O connection
includes this extra 4 bytes at the front of the output assembly described above.
The Command register is a bit string with the following bit definitions.
Byte
Offset
Size
in Bytes
Description
0 4 Command register.
4Up to
492
DeviceNet slave output data.
Table 6-5 Output Assembly Format
Bit Description
0 Local Run Mode. Used in conjunction with the Sys-
tem Run Mode bit in the Run/Idle register to deter-
mine the run mode of the BridgeWay. Both bits must
be set for the BridgeWay to be in Run mode; other-
wise the module will be in Idle mode.
1 Fault. Sets a fault condition in the BridgeWay.
2 Disable DeviceNet network.
3 Not used.
4 Reset the BridgeWay module.
5-31 Not used.
Table 6-6 Output Command Register Bit Definitions