User manual
EtherNet/IP 6-4
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Assembly Objects and Connections
There are 3 Assembly Object instances accessible from EtherNet/IP: input, output
and status. The input and output assemblies are linked to the input and output data
tables. The status assembly provides current status information about the Bridge-
Way.
The assembly instances associated with these 3 assemblies are listed below.
Connection Points
Class 1 connections can be established to these assemblies using the connection
points listed in Table 6-2.
Connection sizes, when connecting to the input and output assemblies can be set
according to the size of the I/O data tables configured in the DeviceNet scanner
and the status and command words in the I/O assemblies. (see the assembly for-
mats below) If a connection is created with a size larger than that configured in the
DeviceNet scanner, the extra data will be filled with 0.
Assembly
Instance
Description Size in Bytes
100 Input 500 max
101 Status 128
150 Output 496 max
Table 6-1 EtherNet/IP Assembly Instances
Conn
Point
Description Size
in Bytes
Use
198 Input-Only
Heartbeat
0 Output connection point
for input-only connections.
199 Listen-Only
Heartbeat
0 Output connection point
for listen-only connections.
100 Input 4-500 Input connection point.
101 Status 128 Input connection point.
150 Output 8-500 Output connection point.
Table 6-2 EtherNet/IP Connection Points