User manual
Quick Start 4-5
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Step 7: Setting the I/O Byte Swapping Option
If it is desirable to have the BridgeWay byte swap each 16-bit word in the I/O
table, the Byte Swap option must be enabled. (see the explanation of this option in
“DeviceNet I/O Configuration” on page 3-17.)
• Highlight the BridgeWay module by left clicking on its icon.
• Select the Device menu option and pull down menu.
• Select the Class Instance Editor option. A pop up Message box appears.
Click on Yes. Another screen appears.
• There are several parts to this screen. Make sure the check box titled Val -
ues in Decimal is NOT checked. At the top right is an Object Address
with 3 text boxes. Set the values in these boxes as follows:
- Class set to 3.
- Instance set to 1.
- Attribute set to 65h.
• To the left of the Object Class section is one titled Service Code. There’s
a text box with a pull down selection titled Description. Pull down the
selections and select “Set Single Attribute”.
• The box titled Data Sent to the Device is now available. At the far left of
this box enter a “01” to enable byte swapping, or a “00” to disable it. Then
click on the Execute button.
• A message should appear in the Data received from device box saying the
execution was completed.
Note: Changes to the byte swapping option do not take effect until the module has
been power cycled.