User manual
Chapter 4 Quick Start 4-1
© 2011 Pyramid Solutions Inc.
Publication PUB-AB7603-014
Quick Start
This chapter provides a step by step explanation of configuration of the Bridge-
Way Ethernet to DeviceNet Gateway. It is intended to be used as a beginner’s
guide to configuring and using the BridgeWay using RSNetWorx for DeviceNet
or NetTool-DN-D. It also demonstrates how easy it is to create your own webpage
and upload it to the module.
DeviceNet Network Configuration
The configuration of the DeviceNet network interface involves using a DeviceNet
node commissioning tool to set the BridgeWay’s MAC ID and baud rate. The fol-
lowing sections explain how this is done using either Rockwell Software’s
RSNetWorx for DeviceNet or HMS’ NetTool-DN-D.
Note: The BridgeWay defaults to 125K baud out of the box. If your DeviceNet
network is not running at 125K baud, the BridgeWay must be powered up on a
local network with the node commissioning tool at 125K baud. Do not attempt to
commission the BridgeWay on a network configured at a different baud rate.
Node Commissioning with BWConfig
See “DeviceNet I/O Configuration” on page 3-17 for an explanation of the
DeviceNet configuration parameters and how they are set using BWConfig.
If BWConfig is used for DeviceNet node commissioning, skip to DeviceNet I/O
Configuration below.