User manual

Configuration 3-15
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
DeviceNet Network Configuration
Setting the DeviceNet Configuration with BWConfig
The DeviceNet network configuration pane in BWConfig contains the parameters
used to control the behavior of the DeviceNet network interface. The parameters
are described in Table 3-2 below. Refer to Figure 3-1 to see how each parameter is
displayed on the user interface.
Parameter Description Allowable
Range
MAC Address The network address the BridgeWay will use
on the DeviceNet network.
The MAC address factory default is 63.
0-63
Baud Rate The baud rate of the DeviceNet network.
The baud rate factory default is 125K
125K
250K
500K
Auto Baud Enable or disable automatic baud rate detec-
tion on the BridgeWay.
The factory default setting for automatic baud
detection is Disabled.
Note: If the BridgeWay is the primary master
on the DeviceNet network, do not enable auto-
matic baud detection.
Enabled or
Disabled
Swap I/O Bytes Enable or disable I/O data byte swapping.
This option will swap bytes in the I/O tables
on 16-bit boundaries. This is helpful when
using Modbus/TCP, which expects data to be
stored in reverse byte orientation from
DeviceNet.
Important: Do not set the Swap I/O option if
an EtherNet/IP Scanner is used with the
BridgeWay. The BridgeWay will be prohib-
ited from entering Run mode.
Enabled or
Disabled
Table 3-2 DeviceNet Network Configuration Parameters