Configuration 3-7
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Network Duplex The duplex setting that the module will use to
communicate on the Ethernet network.
If the network duplex is set to Auto, the mod-
ule will auto-negotiate duplex.
Half, Full, or
Auto
Modbus Timeout The Modbus Timeout option provides a
means to detect the loss of the Modbus Scan-
ner from the Ethernet network. If the option is
enabled, and no Modbus requests are received
within the configured timeout period, the
module Run/Idle status will be set to Idle.
Important: Do not enable the Modbus Time-
out if an EtherNet/IP Scanner is used with the
BridgeWay. The BridgeWay will be prohib-
ited from entering Run mode if there is no
Modbus messages.
0-65000ms
I/O Size The I/O Size parameter provides the means to
configure the maximum size of the Input and
Output Assembly objects. This is useful when
accessing the BridgeWay Assembly object
using Class 3 or UCMM messages with mod-
ules that do not support large assembly buffer
sizes.
The I/O size includes the status and command
headers as well as the DeviceNet slave data.
See “I/O Data Summary” on page 6-10 for
details.
The actual output assembly size will be 4
bytes less than the I/O size configured. Again,
refer to “I/O Data Summary” on page 6-10 for
details.
I/O table sizes below 500 truncate the input
and output tables. Any DeviceNet slave data
that may be mapped beyond the configured I/
O table size will not be transferred to Ethernet.
Suggested maximum sizes for various Ether-
Net/IP devices:
MicroLogix 252
SLC 5/05 248
ControlLogix 500
4-500
Parameter Description Allowable
Range
Table 3-1 Ethernet Network Configuration Parameters