User manual
Installation 2-4
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Connecting DeviceNet
The DeviceNet network connection is a 5-pin terminal block located next to the
power connection on the end of the module. The female terminal block connector
is provided with the BridgeWay. Connections to be made are illustrated in Figure
2-3.
A 120 ohm termination resistor (not provided) may be required for proper net-
work termination. See the DeviceNet Specification for specific rules on
DeviceNet connections and termination.
For information on setting the DeviceNet network configuration (MAC ID, baud
rate, etc.), see “DeviceNet Network Configuration” on page 3-15.
Connecting to Ethernet
The Ethernet connection uses a standard RJ45 connector (not provided). This is
plugged into the socket on the end of the module.
For information on setting the Ethernet IP configuration (IP address, DHCP, etc.),
see “Ethernet Network Configuration” on page 3-6.
Figure 2-3 DeviceNet Connection
(Red) Net Power 24VDC +
(Black) Net Power 24VDC Common
(White) CAN High
(Blue) CAN Low
CAN Shield