User manual

Status and Diagnostics 10-7
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
76 No messages for scanner.
No CAN packets specifically for the DeviceNet scanner have
been received in more than 10 seconds.
This status is only used for the local MAC ID.
77 Incorrect connection size.
The connection size configured in the scanlist entry for the
slave does not match the actual required connection size spec-
ified by the slave.
78 No device response.
A connection could not be established with the slave because
it did not respond.
79 CAN DUP-MAC transmit failure.
The scanner was unable to transmit the duplicate MAC detec-
tion message on the CAN network.
This status is only used for the local MAC ID.
80 In Idle mode.
The device is in Idle mode.
This status is only used for the local MAC ID.
81 In Fault mode.
The device is in Fault mode. Fault mode is set using the Fault
bit in the output command register. i.e. Fault mode is con-
trolled by the EtherNet/IP or Modbus/TCP master controller.
It can be used to indicate a system fault detected at a higher
level. When the device is in Fault mode, all DeviceNet net-
work activity is disabled.
This status is only used for the local MAC ID.
83 Error during slave connection initialization.
An error occurred while creating the I/O connections to the
slave (beyond the identity mismatch or I/O size errors). This
error is triggered by error responses from the slave during the
connection establishment sequence.
Status Code Description
Table 10-6 Node Status Codes (Continued)