User manual
Status and Diagnostics 10-6
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
The page will display the status textually for many of the common status values.
However, to save web page size, a lot of the status values are only displayed
numerically. The following table describes the meaning of each status value.
Status Code Description
0Ok.
Note that this value will be used for nodes both in and out of
the scan list to indicate that there is no issue with the node.
60 Duplicate MAC ID test in progress.
This status is only used for the local MAC ID.
70 Duplicate MAC ID failure.
Another node on the DeviceNet network has the same MAC
ID.
This status is only used for the local MAC ID.
72 Device communications failed.
The I/O connections with a slave have timed out.
73 Incorrect device type.
Device verification has failed with a slave when attempting to
start I/O connections. The level of verification is determined
by the scanlist entry. The following identity information may
be checked during verification depending on the configura-
tion:
Vendor ID
Revision
Device Type
Product Code
75 CAN network quiet.
No CAN packets have been received from the network for
more than 10 seconds.
This status is only used for the local MAC ID.
Table 10-6 Node Status Codes