User manual

Status and Diagnostics 10-5
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Active Slaves Web Page
The Active Slaves page indicates which DeviceNet nodes are currently configured
as slaves to the BridgeWay’s DeviceNet scanner. Each node that is configured as
a slave will be displayed with “Active” next to the node’s MAC ID.
Idle Slaves Web Page
The Idle Slaves page indicates which DeviceNet slaves are currently in the Idle
state. If a node is Idle, the page will display “Idle” next to the node’s MAC ID.
Note that only nodes which are configured as slaves to the BridgeWay and the
BridgeWay itself are updated on this page.
Faulted Slaves Web Page
The Faulted Slaves page indicates which DeviceNet slaves are currently in a
faulted state. If a node is faulted, the page will display “Faulted” next to the
node’s MAC ID. Note that only nodes which are configured as slaves to the
BridgeWay and the BridgeWay itself are updated on this page.
A node is considered faulted if the BridgeWay has lost communications or is
unable to establish communications with the node. The actual problem can be
determined by viewing the Node Status web page.
Invalid Slaves Web Page
The Invalid Slaves page indicates which DeviceNet slaves are not the correct
device type. If a node’s device type is different than that configured in the scan
list, the page will display “Invalid” next to the node’s MAC ID. Note that only
nodes which are configured as slaves to the BridgeWay are updated on this page.
Slave Status Web Page
The Slave Status page displays the current status of all DeviceNet nodes that are
configured as slaves to the BridgeWay and the BridgeWay itself. The status of
each slave is displayed next to the node’s MAC ID. Note that only nodes which
are configured as slaves to the BridgeWay and the BridgeWay itself are updated
on this page.