User manual
Status and Diagnostics 10-4
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
Ethernet Network Status LED
Diagnostic Web Pages
Status and Settings Web Page
The Status and Settings page displays the BridgeWay identification information,
current status, and IP configuration. The IP configuration can be changed from
this page. The module status is updated approximately every 2.5 seconds.
DeviceNet Who Web Page
The DeviceNet Who page displays all devices that have been detected on the
DeviceNet network. Each node that is detected by the BridgeWay will be dis-
played by its device name next to its MAC address. Note that this page does not
update automatically and must be refreshed using the Refresh button provided on
the page.
State Summary Description
Off No Power The module has no power or no IP
address assigned.
Solid Green Network OK
and commu-
nicating
There is at least one EtherNet/IP con-
nection. (Not affected by Modbus/TCP
connections.)
Flashing Green Network OK There are no active connections. (Not
affected by Modbus/TCP connections.)
Solid Red Address con-
flict
The module’s IP address is already in
use by another module.
Flashing Red Connection
Time-out
One or more of the connections in
which this module is the target has
timed out. This state is only left if all
timed out connections are re-estab-
lished or if the module is reset.
Red,Green
Alternate Flashing
Self Test A self test of the module is in progress.
Table 10-5 Ethernet Network Status LED States