36 4 ASCII[4] Status Display Mimics a 4-character alpha-numeric
display.
If there are no faults, the display indi-
cates the BridgeWay MAC ID and its
Run/Idle status.
If there are faults, the display will
scroll through the MAC IDs of the
faulted nodes and display the error
code associated with each. See
Table 10-6, “Node Status Codes,” on
page 10-5 for a list of error codes.
40 1 USINT BridgeWay MAC
ID
The DeviceNet MAC ID of the
BridgeWay.
41 1 USINT Scanner Status The current status of the DeviceNet
scanner. See Table 10-6, “Node Status
Codes,” on page 10-5 for a list of sta-
tus and error codes.
42 1 USINT Scrolling MAC
ID
The scrolling address and status fields
scroll through the address and status
of all DeviceNet slaves that are
faulted. This scrolling includes the
BridgeWay scanner itself.
If there are no faulted nodes, both the
scrolling address and status are set to
0.
The scrolling fields change once a sec-
ond.
43 1 USINT Scrolling Status
44 20 USINT[20] Reserved
64 64 USINT[64] Node Status Table The current status of each DeviceNet
slave node. Each array element is the
status of the node at the corresponding
MAC ID.
If a node is not configured in the
BridgeWay scan list, the status value
will be set to 0.
The BridgeWay scanner status appears
at the entry associated with the
BridgeWay MAC ID.
See Table 10-6, “Node Status Codes,”
on page 10-5 for a list of status codes.