User manual

EtherNet/IP 6-6
© 2004 Pyramid Solutions Inc. Publication PUB-AB7603-008
Output Assembly
The output assembly contains a 32-bit run/idle register and a 32-bit command reg-
ister followed by the data in the BridgeWay’s output data table.
The output data format and content is determined by the DeviceNet scanner con-
figuration. The data appears in the table as it is mapped to the DeviceNet output
connections. The output data in the assembly is 500 bytes long; however, only the
size configured for the output data table will be used, the remaining space will be
ignored.
The Run/Idle register is a bit string with the following bit definitions.
Byte
Offset
Size
in Bytes
Description
0 4 Run/Idle register.
4 4 Command register.
8Up to
500
Output data.
Table 6-5 Output Assembly Format
Bit Description
0 System Run Mode. Used in conjunction with the
Local Run Mode bit in the Command register to
determine the run mode of the BridgeWay. Both bits
must be set for the BridgeWay to be in Run mode;
otherwise the module will be in Idle mode.
1-31 Not used.
Table 6-6 Output Run/Idle Register Bit Definitions