User manual

DeviceNet 5-4
© 2004 Pyramid Solutions Inc. Publication PUB-AB7603-008
Run/Idle Mode
The BridgeWay has two modes of operation, Run and Idle. In both modes the
BridgeWay’s DeviceNet master maintains communication with slave devices in
its scan list.
In Run mode the BridgeWay sends output data to the slaves and receives input
data. Since it is actively sending output data affecting slave device operation, the
BridgeWay rejects attempts to alter its configuration and disrupt communications;
it must first be put in Idle mode.
In Idle mode the BridgeWay still receives input data from the slaves but it does
not send output data. In Idle mode the BridgeWay configuration can be changed.
The Run/Idle mode of the BridgeWay is controlled through the command registers
at the front of the output data from the EtherNet/IP scanner (See “Output Assem-
bly” on page 6-6). The module powers up in Idle mode.
If no EtherNet/IP I/O connection is active, the Run/Idle mode of the BridgeWay is
set through an attribute of the Identity object. To change the Run/Idle mode, use a
DeviceNet messaging tool and send the following message:
Service: Set_Attribute_Single
Class: 1
Instance: 1
Attribute: 103 (67h)
Request Data: 00 for Idle, 01 for Run
Note: When the BridgeWay is reset or powered up, it begins operation in Idle
mode.