User manual
Quick Start 4-7
© 2004 Pyramid Solutions Inc. Publication PUB-AB7603-008
Step 6: Enabling the Autobaud Option
If it is desirable to have the BridgeWay automatically determine the network baud
rate, the Autobaud option must be enabled.
• Highlight the BridgeWay module by right clicking with the cursor on its
icon.
• Select the Device menu option and pull down menu, then select Proper-
ties. A parameter screen is displayed.
• Click on Upload. The parameter values will be read from the device.
• Put the cursor “Autobaud” parameter value. Click to highlight it and then
click again to get a menu. From this menu select “Enable” or “Disable” to
enable or disable the autobaud option respectively.
• Click Download to send the mode change to the BridgeWay.
• Click Close.
Note: Changes to the autobaud option configuration do not take effect until the
module has been power cycled.
Note: If the BridgeWay is the only master on the DeviceNet network, DO NOT
enable autobaud. Automatic baud detection requires there to be traffic on the net-
work, there is typically no traffic until the master establishes connections.