Step 6: Enabling the Autobaud Option
If it is desirable to have the BridgeWay automatically determine the network baud
rate, the Autobaud option must be enabled.
• Highlight the BridgeWay module by left clicking on its icon.
• Select the Device menu option and pull down menu.
• Select the Class Instance Editor option. A pop up Message box appears.
Click on Yes. Another screen appears.
• There are several parts to this screen. Make sure the check box titled Val-
ues in Decimal is NOT checked. At the top right is an Object Address
with 3 text boxes. Set the values in these boxes as follows:
- Class set to 3.
- Instance set to 1.
- Attribute set to 64h.
• To the left of the Object Class section is one titled Service Code. There’s a
text box with a pull down selection titled Description. Pull down the
selections and select “Set Single Attribute”.
• The box titled Data Sent to the Device is now available. At the far left of
this box enter a “01” to enable autobaud, or a “00” to disable it. Then
click on the Execute button.
• A message should appear in the Data received from device box saying the
execution was completed.
Note: Changes to the autobaud option configuration do not take effect until the
module has been power cycled.
Note: If the BridgeWay is the only master on the DeviceNet network, DO NOT
enable autobaud. Automatic baud detection requires there to be traffic on the net-
work, there is typically no traffic until the master establishes connections.