Quick Start 4-3
© 2004 Pyramid Solutions Inc. Publication PUB-AB7603-008
Step 5: Set the DeviceNet MAC ID and Baud Rate
Select the Tools menu option and pull down menu.
Select the Node Commissioning option. Another screen appears.
Click on Browse and choose the DeviceNet network.
When the browse is completed, double click on the BridgeWay icon.
Enter the desired MAC address and/or baud rate, then click the Apply but-
ton.
Note: The BridgeWay will automatically reset if a new MAC ID is entered. If
only the baud rate is changed the BridgeWay must be power cycled before the
new baud rate will take effect.
Note: When the MAC ID is changed, the BridgeWay’s I/O configuration is
cleared.