User manual
Chapter 4 Quick Start 4-1
© 2004 Pyramid Solutions Inc.
Publication PUB-AB7603-008
Quick Start
This chapter provides a step by step explanation of configuration of the Bridge-
Way Ethernet to DeviceNet Gateway. It is intended to be used as a beginner’s
guide to configuring and using the BridgeWay using RSNetWorx for DeviceNet
or NetTool-DN. It also demonstrates how easy it is to create your own webpage
and upload it to the module.
Requirements: An Ethernet network and a PC connected to that network, running
Windows™ 98/ME/2000/XP, Microsoft Internet Explorer 5.5 or higher, a
DeviceNet configuration tool such as Rockwell Software’s RSNetWorx for
DeviceNet or HMS Net Tool-DN. RSLinx version 2.31 or later is required.
DeviceNet Network Configuration
Configuration of the DeviceNet network interface involves using a DeviceNet
node commissioning tool to set the BridgeWay’s MAC ID and baud rate. The fol-
lowing sections explain how this is done using either Rockwell Software’s RSNet-
Worx for DeviceNet or HMS’ NetTool-DN.
Note: The BridgeWay defaults to 125K baud out of the box. If your DeviceNet
network is not running at 125K baud, the BridgeWay must be powered up on a
local network with the node commissioning tool at 125K baud. Do not attempt to
commission the BridgeWay on a network configured at a different baud rate.
Node Commissioning with RSNetWorx for DeviceNet
Step 1: Connect the module to your DeviceNet network.
• Make sure a PC running RSNetWorx for DeviceNet is connected to the
DeviceNet network.
• With the BridgeWay un-powered, connect the DeviceNet network cable
to the DeviceNet connector of the module. (See “Connecting DeviceNet”
on page 2-4)
• Power up the BridgeWay.