User manual
Configuration 3-2
© 2004 Pyramid Solutions Inc. Publication PUB-AB7603-008
DIP Switch Example
The switches are set to 00010100 (20 decimal) (The switch position is shown in
White in the diagram.)
The IP address of the module will be set to 192.168.1.20.
Note: The numbers on the switches on the IP configuration DIP switch do NOT
correspond to bit locations in the address value. In fact, they are reversed. i.e. bit 0
is set by switch 8.
Setting the IP Address Using DHCP/BootP
When DHCP/BootP is enabled and a DHCP or BootP server is found, the IP
address, Subnet mask, and Gateway address is automatically configured by the
DHCP/BootP server. It can be enabled using the BridgeWay’s Settings web page.
Note: The use of DHCP is the default configuration for the BridgeWay as
shipped.
Figure 3-1 IP Configuration DIP Switch