User manual

Chapter 3 Configuration 3-1
© 2004 Pyramid Solutions Inc.
Publication PUB-AB7603-008
Configuration
This chapter describes how the BridgeWay Ethernet to DeviceNet Gateway is
configured. The next chapter walks the reader through the configuration of the
BridgeWay using the commonly available configuration tools.
Ethernet Network Configuration
Several methods may be used to set the IP Address. These methods include;
IP Address Configuration Switch, DHCP/Bootp protocol, web browser, and the
ARP protocol.
Setting the IP Address with the Configuration Switch
If DHCP/BootP is not enabled or a server is not found and the Configuration
Switch is non zero, on power up the value of the switch is used to form an the IP
Address. The switch represents the binary value of the last byte in the 4 byte IP
address. In this case it is n.
IP address: 192.168.1.n
Subnet mask: 255.255.255.0
Gateway address: 0.0.0.0 (No gateway set)
This is a private address and can only be used on a local intranet. In such a case a
Web Browser such as Microsoft’s Internet Explorer can be used to access the
BridgeWay’s web page which allows changing the IP Address, Subnet mask, and
GateWay address settings.