User manual

Status and Diagnostics 10-4
© 2004 Pyramid Solutions Inc. Publication PUB-AB7603-008
Ethernet Network Status LED
Diagnostic Web Pages
Status and Settings Web Page
The Status and Settings page displays the BridgeWay identification information,
current status, and IP configuration. The IP configuration can be changed from
this page. The module status is updated approximately every 2.5 seconds.
Active Nodes Web Page
The Active Nodes page indicates which DeviceNet nodes are currently configured
as slaves to the BridgeWay’s DeviceNet scanner. Each node that is configured as a
slave will be displayed with “Active” next to the nodes MAC ID.
Idle Nodes Web Page
The Idle Nodes page indicates which DeviceNet nodes are currently in the Idle
state. If a node is Idle, the page will display “Idle” next to the node’s MAC ID.
Note that only nodes which are configured as slaves to the BridgeWay and the
BridgeWay itself are updated on this page.
State Summary Description
Off No Power The module has no power or no IP
address assigned.
Solid Green Network OK
and commu-
nicating
There is at least one EtherNet/IP con-
nection. (Not affected by Modbus/TCP
connections.)
Flashing Green Network OK There are no active connections. (Not
affected by Modbus/TCP connections.)
Solid Red Address con-
flict
The modules IP address is already in
use by another module.
Flashing Red Connection
Time-out
One or more of the connections in
which this module is the target has
timed out. This state is only left if all
timed out connections are re-estab-
lished or if the module is reset.
Red,Green
Alternate Flashing
Self Test A self test of the module is in progress.
Table 10-5 Ethernet Network Status LED States