User Manual

41
5.2.2 Replacement of Control Module (BMS)
5.2.2.1 Turn off the whole battery strings power. Must confirm the D+ and D- terminal are
without power. The turn off progress refer to chapter 3.5.4.
5.2.2.2 Dismantle D+ and D- Power Cable, Communication Cable and Grounding Cable.
5.2.2.3 Dismantle the control Module’s fix screw of left and right side. And dismantle the fix
metal brackets.
5.2.2.4 Remove the control module.
Danger: when battery is connected together with the base the internal socket still have
high voltage DC power from serial connected battery modules (battery module can’t be
turned off).
5.2.2.5 Pile up the new control module.
5.2.2.6 Install back the control Module’s fix screw of left and right side. And Install back the fix
metal brackets.
5.2.2.7 Install back Grounding Cable, Communication Cable and the D+ and D- Power Cable.
5.2.2.8 Turn on this battery string. Refer to chapter 3.5.4.
5.3 Battery Maintenance
Danger: The maintenance of battery must be done by qualified and authorized personnel
only.
Danger: Some maintenance items must turn off at first.
5.3.1 Voltage Inspection:
[Periodical Maintenance] Check the voltage of battery system through the monitor system. Check
the system whether exist abnormal voltage or not. For example: Single cell’s voltage is abnormal
high or low.
5.3.2 SOC Inspection: