Operating instructions
8 Installation and Operating Instructions
Lifting Station Type ABS Nirolift. Lifting Station Type ABS Sanisett.
5.7 Locationofpowersupplycableandoatswitch
The connection cable for the pump is fed through the cable pipe and brought into the room where the power
supply is located by means of a branch pipe (T-piece). The connection cable is fed through the slot in the cable
inletandthecableinletitselfispushedrmlyintothebranchpipe.
NOTE: In the case of twin units the connection cables for the oat switches should be laid in
a similar manner to the pump power cable.
1. Branch pipe (T-piece)
2. Cable inlet
3. Vent line
4. Motor connection cable
1067-00
Figure 7: Cable inlet
5.8 Installation of the control unit
ATTENTION! The control unit should be tted above possible ood level in a well ventilated room
and in an easily accessible position. Protection Class of the control unit IP 54.
Thecontrolunitshouldbesecuredatallxingpoints.Thexingholesareaccessibleafterunscrewingthe
lower housing cover.
ATTENTION! Do not drill through the housing of the control unit itself.
NOTE: A number of different control box models exist. Please check the wiring diagram/
instruction manual in the control box.
6 Commissioning
m
The safety hints in the previous sections must be observed!
Before commissioning, the unit should be checked and a functional test carried out. Particular attention should
be paid to the following:
- Have the electrical connections been carried out in accordance with regulations?
- Is the motor overload switch correctly set?
- Havethepowerandcontrolcircuitcablesbeencorrectlytted?
- Was the sump cleaned out?
- Havetheinowandoutowsofthepumpstationbeencleanedandchecked?
- Is the direction of rotation correct, even if run via an emergency generator?
- Are the level controls functioning correctly?
- Aretherequiredgatevalves(wheretted)open?
- Dothenon-returnvalves(wheretted)functioneasily?
ATTENTION! Before commissioning, the collection tank should be cleaned of any large particles
and lled with water. After commissioning, the lifting unit is normally operated with
the selector switch in position “Auto”.