Output to AC grid connection:
The PVI 3000-5300 is designed to feed power into a standard 60Hz, 240 or 208V AC utility service or 208V AC provided
within a facility by a step down transformer (for example, from 480V AC service). As required by NEC, there must be a
dedicated 2-pole circuit breaker for the PV inverter connection. This circuit breaker (and wiring) must have a rating of 20, 25
or 30A depending on the model. The inverter is designed to work with the range of AC voltage for a 240VAC or 208V
service defined by UL1741/IEEE1547.