Technical data
PVI 3000/4000/5000/5300 Installation and Operation Manual
42
VacL
The AC voltage of mains utility is below the
lower limit.
Verify setting for S201 is correct for the
grid voltage applied
Measure the AC voltage and compare to
the voltage on the inverter display
Contact Solectria Renewables for
assistance if the range needs to be
adjusted
FacH
The frequency of AC voltage of the utility is
above the upper limit.
Measure the frequency and compare to
the frequency on the display
Contact Solectria Renewables for
assistance if the range needs to be
adjusted
FacL
The frequency of AC voltage of the utility is
below the lower limit.
Measure the frequency and compare to
the frequency on the display
Contact Solectria Renewables for
assistance if the range needs to be
adjusted
VpvH
The DC voltage of PV array is above the upper
limit.
Turn off the inverter
Measure the VDC at the Inverter
disconnect if over 599VDC the solar
array needs to be inspected
Contact installing company
Do not turn on the inverter until the
condition is repaired
Imax_AC
Over current on the AC side.
The inverter will continue to operate at a
lower current
If message occurs frequently contact the
installing company
InvTempMax
The internal temperature of the inverter
exceeded the safe operating limit.
If the inverter is located in direct
sunlight it may need to be shaded
The VDC input may be too high causing
increased temperature, reduce VDC
input. Contact installing company or
Solectria Renewables
Relay Open
Relay Close
Relay test failed. Contact installing company or Solectria
Renewables
VacL1 H
The voltage between L1 and neutral is over the
upper limit.
Verify setting for S201 is correct for the
grid voltage applied
Measure the AC voltage and compare to
the voltage on the inverter display
Contact Solectria Renewables for
assistance if the range needs to be
adjusted
VacL1 L
The voltage between L1 and neutral is under
the lower limit.
Verify setting for S201 is correct for the
grid voltage applied
Measure the AC voltage and compare to
the voltage on the inverter display
Contact Solectria Renewables for
assistance if the range needs to be
adjusted
VacL2 H
The voltage between L2 and neutral is over the
upper limit.
Verify setting for S201 is correct for the
grid voltage applied
Measure the AC voltage and compare to
the voltage on the inverter display
Contact Solectria Renewables for
assistance if the range needs to be
adjusted
VacL2 L
The voltage between L2 and neutral is under
the lower limit.
Verify setting for S201 is correct for the
grid voltage applied
Measure the AC voltage and compare to
the voltage on the inverter display
Contact Solectria Renewables for