User Guide

6 Installation & Operation Manual Copyright © Puretec Pty Ltd 2023
The control valve, fittings and/or bypass are designed to accommodate minor plumbing
misalignment but are not designed to support the weight of a system or the plumbing.
The unit must be installed on a surface that is firm, level, horizontal in both directions
and fully supports the entire base of the soener. The soener can weigh a considerable
amount when full and the base must be suitable to support this weight.
Do not use petroleum jelly, oils, other hydrocarbon lubricants or spray silicone anywhere.
A silicon lubricant may be used on the black o-rings but it is not necessary.
Do not use pipe dope or other sealants on threads. Thread seal tape is the preferred
sealant but is not necessary on the nut connection or caps because of o-ring seals.
All plumbing should be done in accordance with local plumbing codes. The pipe size for
the drain line should be a minimum of ⅝”.
Avoid getting primer and solvent cement on filter system.
Install grounding strap on metal pipes if required.
Ensure the system is protected against high pressure and extreme temperatures.
Chlorine (free chlorine) tolerance is 1ppm - high chlorine levels permanently damage
the soening resin & is not covered under warranty. If chlorine exceeds this limit, we
recommend a carbon pre-filter such as the WH2 or CFS Series. Please refer to Puretec
for a specific recommendation. In any case, a carbon pre-filter is recommended to
protect against chlorine spikes & prolong the resin life.
If pressure exceeds 500 kPa an approved pressure limiting device needs to be fitted.
Things to Remember While Planning Your Installation:
All installation procedures MUST conform to local plumbing codes.
If lawn sprinklers, a swimming pool, or geothermal heating/cooling or water for other
devices/activities are to be treated by the water soener, a larger model MUST be
selected to accommodate the higher flow rate plus the backwashing requirements of
the water soener. Contact Puretec for assistance.
Before Installation
WARNING - THESE STEPS ARE CRITICAL FOR THE CORRECT
INSTALLATION OF YOUR WATER TREATMENT SYSTEM.