Technical information
Deltabar M PMD55
Endress+Hauser 33
Human interface
Local operation Operating keys and elements located on the electronic insert
Function of the DIP switches
P01-Mxxxxxxx-19-xx-xx-xx-012
HART electronic insert
1 DIP switch for locking/unlocking parameters
relevant to the measured value
2 DIP switch for switching damping on/off
3 DIP switch for alarm current SW / Alarm Min
(3.6 mA)
4 DIP switch for defining operating mode and
output characteristics
5 DIP switch for defining high pressure side
6 Slot for optional local display
7 Green LED to indicate successful operation
8 Operating keys for lower range value (zero)
and upper range value (span)
P01-Mxxxxxxx-19-xx-xx-xx-013
PROFIBUS PA electronic insert
1 DIP switch for locking/unlocking parameters
relevant to the measured value
2 DIP switch for switching damping on/off
3Not used
4 DIP switch for defining operating mode and
output characteristics
5 DIP switch for defining high pressure side
6 DIP-switch for hardware address
7 DIP-switch for bus address SW / HW
8 Slot for optional local display
9Operating key for position zero adjustment
or reset (Zero)
10 Green LED to indicate successful operation
P01-Mxxxxxxx-19-xx-xx-xx-014
FOUNDATION Fieldbus electronic insert
1 DIP switch for locking/unlocking parameters
relevant to the measured value
2 DIP switch for switching damping on/off
3 DIP-switch for simulation mode
4 DIP switch for defining operating mode and
output characteristics
5DIP switch for defining high pressure side
6 Slot for optional local display
7 Green LED to indicate successful operation
8 Operating key for position zero adjustment
or reset (Zero)
➂➁
➅
on
off
SW / P2=High
SW / Alarm min
SW / Ö
damping
1
2
3 4 5
➃➄
➀
➆
➇
on
off
Display
Zero
Span
HART
R
FIELD COMMUNICATION PROTOCOL
SW / P2=High
delta p only
SW / Alarm min
SW / Ö
damping
➂➁
➅
on
off
SW / P2=High
damping
1
2
3 4 5
➃➄
➀
➇
on:P2=
delta p
only
High off:SW
1
2
3
4
5
off:SW
on:
Ö
on
off
damp
not used
Address
SW
HW
Zero
on
off
Display
➆
9
10
SW / Ö
➂➁
➅
on
off
SW / P2=High
Simulation
SW / Ö
damping
1
2
3 4 5
➃➄
➀
➆
➇
on
off
Display
Zero
simulation
TM
F
OUNDATION
SW / P2=High
SW / Ö
damping
delta p only
Switch Symbol/
label
Switching position
"off" "on"
1 The device is unlocked.
Measured-valaue-relevant parameters can be
changed.
The device is locked.
Measured-value-relevant parameters can not
be changed.
2damping The damping is switched off.
The output signal reacts immediately to
changes of the measured value.
The damping is switched on.
The output signal reacts to changes of the
measured value with the delay time .
1
1) The value of the delay time can be set in the operating menu.
Factory setting: = 2 s or as per order specifications.
3 (HART) SW/Alarm min The alarm current is as defined in the
operating menu.
The alarm current is 3,6 mA irrespective of
the setting in the operating menu.
3 (FF) Simulation The simulation mode is switched off (Factory
setting).
The simulation mode is switched on.
4SW/ The output characteristics is as defined in the
operating menu.
The output characterisitc is "Square root",
irrespective of the settings in the operating
menu.
5 SW/P2= High The high pressure side is as defined in the
operating menu.
The high pressure side is allocated to the P2
pressure connection, irrespective of the
setting in the operating menu.