Technical information

Deltabar M PMD55
Endress+Hauser 3
Function and system design
Measuring principle
P01-PMD55xxx-03-xx-xx-xx-001
Measuring cell of the Deltabar M
1 Sensing element
2 Overload diaphragm/Middle diaphragm
3 Filling oil
4 Process isolating diaphragm
The separating diaphragms (4) are deflected on both sides by the acting pressures p
1
and p
2
. A filling oil (3)
transfers the pressure to a resistance circuit bridge (semi-conductor technology). The differential-pressure-
dependent change of the bridge output voltage is measured and further processed.
Level measurement (level,
volume and mass)
Design and operation mode
P01-PMD55xxx-15-xx-xx-xx-002
Level measurement with Deltabar M;
left: V1 version; vertical impulse lines; 90° alignment
middle: H1 version; horizontal impulse lines; 180 ° alignment
right: H2 version; horizontal impulse lines; 90° alignment
h Height (level)
p Differential pressure
Density of the medium
g Gravitation constant
Your benefits
Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve
Choice of diverse level units
Has a wide range of uses, e.g.
for level measurement in tanks with superimposed pressure
in the event of foam formation
in tanks with agitators of screen fittings
in the event of liquid gases
for standard level measurement
1
p
2
p
1
2
3
4
h=
Dp
r g
+
h
PMD55, H1
h=
Dp
r g
+
h
PMD55, H2
h=
Dp
r g
+
h
PMD55, V1