Technical information

Deltabar M PMD55
Endress+Hauser 17
Supply voltage Note!
When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas
ä 42, sections "Safety Instructions" and "Installation/Control drawing".
4 to 20 mA HART
PROFIBUS PA
Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
Start-up current HART 12 mA or 22 mA (selectable)
Current consumption PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Cable entry See product structure, ä 39, feature 050 "Electrical connection".
Cable specification Endress+Hauser recommends using shielded, twisted-pair two-wire cables.
Terminals for wire cross-sections 0.5...2.5 mm
2
(20...14 AWG)
Cable external diameter: 5...9 mm (0.2...0.35 in)
Residual ripple Without influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply 0.001% of URL/V
Type of protection Supply voltage
Intrinsically safe 11.5 ... 30 V DC
Other types of protection
Devices without certificate
11.5 ... 45 V DC (Versions with plug-in connection 35 V DC)