Installation manual
Table Of Contents
- Table of Contents
- 1 System Outline
- 2 Activation Key Installation
- 3 Installation
- 3.1 Before Installation
- 3.2 Installation of the PBX
- 3.2.1 Unpacking
- 3.2.2 Names and Locations
- 3.2.3 Opening/Closing the Front Cover
- 3.2.4 Attaching Fan Guards
- 3.2.5 Installation of Basic System or 2-shelf System (Floor Standing)
- 3.2.6 Installation of 3- or 4-shelf System (Tower Type)
- 3.2.7 Installation of 4-shelf System (Side-by-side Type)
- 3.2.8 Wall Mounting (KX-TDE600/KX-TDE620)
- 3.2.9 Installing/Replacing the Power Supply Unit
- 3.2.10 Frame Ground Connection
- 3.2.11 Installing/Removing the Optional Service Cards
- 3.2.12 Cable Handling
- 3.2.13 Types of Connectors
- 3.2.14 Attaching a Ferrite Core
- 3.2.15 Fastening Amphenol Connector
- 3.2.16 Surge Protector Installation
- 3.3 Information about the Main Processing Card
- 3.4 Information about the Virtual Cards
- 3.5 Information about the Optional Shelf Expansion Cards
- 3.6 Information about the Built-in Shelf Expansion Card
- 3.7 Information about the CO Line Cards
- 3.8 Information about the Extension Cards
- 3.8.1 CSIF4 Card (KX-TDA0143) and CSIF8 Card (KX-TDA0144)
- 3.8.2 DHLC8 Card (KX-TDA0170)
- 3.8.3 DLC8 Card (KX-TDA0171)
- 3.8.4 DLC16 Card (KX-TDA0172)
- 3.8.5 SLC8 Card (KX-TDA0173)
- 3.8.6 EXT-CID Card (KX-TDA0168)
- 3.8.7 CSLC16 Card (KX-TDA0177), ESLC16 Card (KX-TDA6174), EMSLC16 Card (KX-TDA6175), and ECSLC24 Card (KX-TDA6178)
- 3.8.8 IP-EXT16 Card (KX-TDA0470)
- 3.9 Information about the Other Cards
- 3.10 Connection of Extensions
- 3.11 Connection of Doorphones, Door Openers, External Sensors, and External Relays
- 3.12 Connection of Peripherals
- 3.13 LAN Connection
- 3.14 Power Failure Connections
- 3.15 Starting the PBX
- 4 Guide for the Maintenance Console
- 5 Troubleshooting
- 6 Appendix
- Index

3.2.10 Frame Ground Connection
1. Loosen the screw.
2. Insert a grounding wire (user-supplied).
3. Tighten the screw.
4. Connect the grounding wire to ground.
5. Repeat steps 1 to 4 for each shelf.
Screw
To ground
Grounding
wire
WARNING
• Proper grounding (connection to ground) is very important to reduce the risk to the user of
electrocution or to protect the PBX from the bad effects of external noise in the case of a
lightning strike.
• The grounding wire of the AC cable has an effect against external noise and lightning strikes,
but it may not be enough to protect the PBX. A permanent connection between ground and the
ground terminal of each PBX must be made.
CAUTION
• Make sure to separately connect the frame of each shelf to a different ground terminal. Do not connect
it to other shelves.
• For grounding wire, green-and-yellow insulation is required, and the cross-sectional area of the
conductor must be more than 0.75 mm
2
or 18 AWG.
Notice
Be sure to comply with applicable local regulations (e.g., laws, guidelines).
In most of the continental United States, the ground provided by the "Third wire ground" at the commercial
power outlet will be satisfactory. However, in a small percentage of cases this ground may be installed
incorrectly. Therefore, the following test procedure should be performed.
Test Procedure
1. Obtain a suitable voltmeter and set it for a possible reading of up to 250 V AC.
2. Connect the meter probes between the 2 main AC voltage points on the wall outlet. The reading obtained
should be 108 V AC to 132 V AC.
3. Move one of the meter probes to the 3rd prong terminal (GND).
Either the same reading or a reading of 0 volt should be obtained.
4. If a reading of 0 volt at one terminal and a reading of 108 V AC to 132 V AC at the other terminal is not
obtained, the outlet is not properly grounded.
This condition should be corrected by a qualified electrician (per article 250 of the National Electrical Code).
5. If a reading of 0 volt at one terminal and a reading of 108 V AC to 132 V AC at the other terminal is obtained,
then set the meter to the "OHMS/RX1" scale, place one probe at the GND Terminal and the other probe
at the terminal which gave a reading of 0 volt.
A reading of less than 1 ohm should be obtained. If the reading is not obtained, the outlet is not adequately
grounded. See qualified electrician.
Document Version 2009-12 Installation Manual 113
3.2.10 Frame Ground Connection