Specifications

EMC-CS-2009.1
© Copyright Ford Motor Company – All Rights Reserved Page 107 of 121
February 11, 2010
D.4 Transient Application Mode
Application of transient pulses A1, A2 and C to the DUT are facilitated using three different operating modes.
Mode 1 represents a condition where the test pulse is applied at a fixed repetition rate as shown in Table D-1 below. Mode 1
is applicable for pulses A1 and A2 only when applied to DUT switched power supply circuits.
Table D-1: CI 220 Mode 1 Characteristics
Transient Pulse
Pulse Repetition Rate
(PRR)
Duration
A1
A2-1
0.2 Hz,
10% duty cycle
120 sec
Mode 2 represents a condition where test pulses are applied using a pseudo- random timing sequence as illustrated in Figure
D-11. Mode 2 is only used with test pulse A1 when applied to DUT inputs. The time "T" is 50 ms.
Mode 3 represents a condition where test pulses are applied using pseudo- random bursts as illustrated Figure D-12. The
timing sequence is identical to that used for Mode 2. Mode 3 is used only with test pulses A2-1, A2-2, C-1, and C-2. The
bust time "T" is 50ms.
Modes 2 and 3 is also used when performing testing per RI 130 (see section 13).. Modes 1, 2 and 3 are produced by the
transient generator circuit presented in Annex F.
Figure D-11: CI 220 Mode 2 Characteristics
T
7T
5T T
T5T T
7T
T
2T T
3T
7T
T
T
7T
3T T
T5T
T
T
T
T = 50 msec
Pulse Timing
Sequence
Resulting Transient
Sequence