User Instructions

4
2. Installation.
2.1. Requirements.
The unit should be mounted in confined spaces, in accordance with the 2nd environmental class, with normal
relative humidity (RH=90 % maximum, without condensation) and temperature from -10 °C to +40 °C. Ensure the free
flow of air around the unit. The PSU shall work in a vertical position that guarantees sufficient convectional air-flow
through ventilating holes of the enclosure.
The switch load balance should be done before installation. The given value of 30 W per port is the maximum
value referring to a single output. The total power consumption should not exceed 240 W. The increased demand for
power is particularly evident in the case of cameras with heaters or infrared illuminators - when launching these features,
the power consumption increases rapidly, which may adversely affect the operation of the switch. As the device is
designed for a continuous operation and is not equipped with a power-switch, therefore an appropriate overload protection in
the power supply circuit should be provided. The electrical system shall be made in accordance with applicable standards and
regulations.
2.2. Installation procedure.
1. Connect the 230 V power supply and turn on the device. The connection should be made with the supplied 3-core
cable with a plug. The place and method of installation of the switch should ensure free air flow around the unit.
2. Connect the camera wires to the RJ45 connectors (sockets RJ45 from 1 to 24).
3. Connect the remaining LAN devices to RJ45 connectors or SFP socket (G1/TP and G1/SFP or G2/TP and G2/SFP)
CAUTION! G1/TP and G1/SFP or G2/TP and G2/SFP connectors can not operate simultaneously!
4. Check the optical indication of switch operation (see Table 3).
Connection schemes