User Instructions
4 
 2. Installation. 
2.1. Requirements. 
  The  unit  should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal 
relative humidity (RH=90 % maximum, without condensation) and temperature from -10 °C  to  +40 °C.  Ensure  the  free 
flow  of  air  around  the  unit.  The  PSU  shall  work  in  a  vertical  position  that  guarantees  sufficient  convectional  air-flow 
through ventilating holes of the enclosure.  
 The switch load balance should be done before installation. The given value of 30 W per port is the maximum 
value referring to a single output. The total power consumption should not exceed  240 W. The increased demand for 
power is particularly evident in the case of cameras with heaters or infrared illuminators - when launching these features, 
the  power  consumption  increases  rapidly,  which  may  adversely  affect  the  operation  of  the  switch.  As  the  device  is 
designed for a continuous operation and is not equipped with a power-switch, therefore  an appropriate overload protection in 
the power supply circuit should be provided. The electrical system shall be made in accordance with applicable standards and 
regulations. 
2.2. Installation procedure. 
1. Connect the 230 V power supply and turn on the device. The connection should be made with the supplied 3-core 
cable with a plug. The place and method of installation of the switch should ensure free air flow around the unit. 
2. Connect the camera wires to the RJ45 connectors (sockets RJ45 from 1 to 24). 
3. Connect the remaining LAN devices to RJ45 connectors or SFP socket (G1/TP and G1/SFP or G2/TP and G2/SFP) 
CAUTION! G1/TP and G1/SFP or G2/TP and G2/SFP connectors can not operate simultaneously! 
4. Check the optical indication of switch operation (see Table 3). 
 Connection schemes 





