User Instructions

www.pulsar.pl RSGUPS108R RACK POWER
6
Electrical parameters (tab. 4).
Mains supply
230V AC (-15%/+10%) 50Hz
Current up to
1,3A max./ 230V AC
Supply power
196W max.
Output voltage at the PoE ports
Output voltage the recorder NVR
52V DC maintained regardless of the state of battery charge
12V DC maintained regardless of the state of battery charge
The output current at the PoE ports
8 x 0,6A Ʃ=2,3A (max.)
Output current of the recorder NVR
4A
Ripple voltage output of the NVR recorder
150 mV p-p max.
Battery charge current
(batteries 2x7Ah / 2x17Ah / 2x28Ah, connect
batteries in series)
1A max. (+/-5%)
Approximate backup time
5h 30min
Short-circuit protection SCP and overload
protection OLP
105% ÷ 150% of the PSU power, manual restart
(failure requires the disconnection of the DC output)
PSU current consumption
300mA/27,6V
Battery circuit protection SCP and reverse
polarity connection
melting fuse
Excessive discharge protection UVP
U<19V (+/-5%) disconnect of connection battery
Optical indication of operation:
LED: AC, DC, TEMP, LoB, ALARM, LINK, PoE
Acoustic operation indication:
Piezoelectric indicator ~75dB/0,3m
The ALARM technical output of collective failure
Relay type: 1A@ 30VDC/50VAC
The F
MAINS
fuse in the 230V power supply circuit
T 6,3A
Mechanical parameters (tab. 5).
Mounting dimensions
W=19”, H=2U, D=307
Dimensions
W=482, W1=442, H=88, D=307, D1=32, D2=10 [+/- 2mm]
Fixation
four-point butt mounting to RACK profiles the set include 4 M6 screws + cage nuts
Net weight
7,1kg / 7,6kg
Enclosure
Steel plate RAL 9005, black
Connectors
230V AC input: the IEC C14 socket with a fuse, power cable 2m (included)
Technical output ALARM: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2
Power supply output of the NVR recorder: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2
,
power cord 2m, terminated with the DC 5,5/2,1 plug (included)
Outputs of cameras PoE: sockets RJ45 8P8C
Data output of the UPLINK recorder: RJ45 8P8C jack
Battery output BAT: 6,3F-2,5
Notes
Forced cooling (fan).
Operation safety (tab.6).
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC