User Instructions
4
Table 3. Electrical parameters
Mains supply
~230 V; 50 Hz
Current up to
1,5 A
Supply power
267 W
The output current at the PoE (RJ45) ports
16 x 0,6 A ΣI=4 A (max.)
Output voltage at the PoE (RJ45) ports
54 V DC
NVR output – recorder
12 V DC / 4 A (max.)
PSU current consumption
250 mA
Battery charge current
(batteries 4x7 Ah / 4x17 Ah, connect batteries in series)
0,5 A max. /4x12 V (+/-5 %)
Approximate backup time
4 h
Battery circuit protection SCP and reverse polarity
connection
melting fuse
Excessive discharge protection UVP
U<38 V (± 5 %) – disconnect of connection battery
Table 4. Mechanical parameters
Mounting dimensions
W=19”, H=2U, D=348
Dimensions
W=482, W
1
=446, H=88, D=348, D
1
=32, D
2
=15 [+/- 2 mm]
Net/gross weight
6,5 / 7,0 kg
Enclosure
Steel plate, DC01 1,0mm color: black RAL 9005
Fixation
four-point butt mounting to RACK profiles – the set include 4 M6 screws + cage nuts
Connectors
Power supply of the cameras: RJ45 socket
Output of recorder: RJ45 socket or SFP
The recorder power supply output: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm2 , power cord 2 m, terminated
with the DC 5,5/2,1 plug (included)
Outputs: Φ 0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5
Notes
Forced cooling (fan).
Table 5. Operation safety
Protection class PN-EN 609501:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP 20
Electrical strength of insulation:
- between input and output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
3000 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500 V DC
Declarations
CE
Table 6. Operating parameters
Operating temperature
-10 ºC...+45 ºC
Storage temperature
-20 ºC...+60 ºC
Relative humidity
20 %...90 %, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106