Excessive discharge protection UVP
U<19 V (+/-5 %) disconnect of connection battery
Optical indication of operation:
LED: AC, DC, TEMP, LoB, ALARM, LINK, PoE
Acoustic operation indication:
Piezoelectric indicator ~75 dB/0,3 m
The ALARM technical output of collective failure
Relay type: 1 A@ 30 V DC/50 V AC
The F
MAINS
fuse in the 230 V power supply circuit
T 3,15 A
Mechanical parameters (tab. 5).
Mounting dimensions
W=19”, H=2U, D=368
Dimensions
W=482, W
1
=442, H=88, D=368, D
1
=32, D
2
=10 [+/- 2 mm]
Fixation
four-point butt mounting to RACK profiles the set include 4 M6 screws + cage nuts
Net weight
7,3 kg / 7,9 kg
Enclosure
Steel plate RAL 9005, black
Connectors
230 V input: the IEC C14 socket with a fuse, power cable 1,5 m (included)
Technical output ALARM: Φ0,5-2,1 (AWG 24-12) 0,5-1,5 mm
2
Outputs of cameras PoE: sockets RJ45 8P8C
Data output of the UPLINK recorder: RJ45 8P8C jack
Battery output BAT: 6,3F-2,5
Notes
Forced cooling (fan).
Operation safety (tab.6).
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU
- between input circuit and protection circuit
- between output circuit and protection circuit
3000 V AC min.
1500 V AC min.
500 V AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500 V DC
Operating parameters (tab.7).
Environmental class
II
Operating temperature
-10 ºC...+40 ºC
Storage temperature
-20 ºC...+60 ºC
Relative humidity
20 %...90 %, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106