User Instructions

www.pulsar.pl RPUPS1248R RACK POWER
5
Electrical parameters (tab. 2).
Mains supply
176÷264V AC
Current up to
1,5A@230V AC max.
Supply power
264W max.
Efficiency
82%
Power factor PF
>0,95@230V AC
Output voltage PoE for cameras
Output voltage NVR recorder
44V ÷ 54V DC buffer operation
38V ÷ 54V DC battery-assisted operation
12V DC maintained regardless of the state of battery
charge
Output current for cameras
12 x 0,3A (I = 3,5A max.)
Output current for recorder
4A
Battery charge current (batteries 4×7Ah / 4×17Ah,
connect batteries in series)
0,5A max. (+/-5%)
Approximate backup time
8h 15min
Ripple voltage cameras output
150 mV p-p max.
Ripple voltage recorder output
100 mV p-p max.
PSU current consumption
150 mA
Short-circuit protection SCP
cameras: 12 x PTC 1A, polymer fuse
recorder: 1 x PTC 5A, polymer fuse
Overload protection OLP
105% ÷ 150% of the PSU power, automatic return
Overvoltage protection OVP
>62V (activation requires disconnecting the load or supply
for about 20 s.)
Battery circuit protection SCP and reverse
polarity connection
glass fuse
Surge protection
varistors
Optical indication of operation:
LED: AC, DC, LoB, TEMP, ALARM, NVR
Acoustic operation indication:
Piezoelectric indicator ~75dB/0,3m
The ALARM technical output of collective failure
Relay type: 1A@ 30V DC / 50V AC
The F
MAINS
fuse in the 230V power supply circuit
T 6,3A
Mechanical parameters (tab. 3).
Mounting dimensions
W=19”, H=2U, D=267
Dimensions
W=482, W
1
=442, H=88, D=267, D
1
=32, D
2
=10 [+/- 2mm]
Fixation
four-point butt mounting to RACK profiles the set include 4 M6 screws + cage nuts
Net / gross weight
6,0kg / 6,4kg
Enclosure
Steel plate RAL 9005, black
Connectors
230V AC input: the IEC C14 socket with a fuse, power cable 1,5m
(included)
Technical output ALARM: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2
Power supply output of the NVR recorder: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2
,
power cable 2m (included)
PoE cameras power supply output: socket RJ45 8P8C
Battery output BAT: 6,3F-2,5
Notes
Forced cooling (fan)