User Instructions
www.pulsar.pl ROUPS12V RACK POWER
5
Mechanical parameters (tab. 3).
Mounting dimensions
W=19", H=2U, D=262
Dimensions
W=482, W
1
=442, H=88, D=262, D
1
=5, D
2
=32 [+/- 2mm]
Fixation
four-point butt mounting to RACK profiles – the set include 4 M6 screws + cage nuts
Net/gross weight
5,7kg / 6,2kg
Enclosure
Steel plate RAL 9005, black
Connectors
230V AC input: the IEC C14 socket with a fuse, power cable 1,5m
(included)
Technical output: ALARM: Φ0,5-2,1 (AWG 24-12) 0,2-1,5mm
2
Outputs AUX, BAT: Φ0,5-3,2 (AWG 24-8) 0,5-4mm
2
Notes
Forced cooling (fan).
Operation safety (tab.4).
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating parameters (tab.5).
Environmental class
II
Operating temperature
-10ºC...+45ºC
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation.
2.1. Requirements.
The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall be
mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max. without
condensation) and the temperature from -10°C do +45°C.
During normal operation the total current consumption of the cameras cannot exceed
I=18A. Maximum battery charging current is: 2A.
Total device current + battery: 20A max.
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an
appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user shall be informed
about the method of unplugging (usually through assigning an appropriate fuse in the fuse-box). The electrical system
shall follow valid standards and regulations.