Data Sheet

Table Of Contents
RLB8 v.1.0/II
RACK 8x2A fuse strip
CODE
NAME:
:
DESCRIPTION
F
The RLB8 fuse strip is designed for power distribution in low-voltage systems requiring voltage in the range 10 V
÷ 56 V DC ( e.g. RACK uninterruptible power supply of the ROUPS series, etc.). It is fitted with the DC INPUT for power
supply and 8 independently protected outputs AUX1 ÷ AUX8. Each AUX output is equipped with short-circuit protection
(SCP), in the form of a 2 A fuse. Output state is indicated by L1 ÷ L8 LEDs. Fuse failure is indicated by switching off the
appropriate LED: L1 for AUX1, etc. Additionally, in the case of failure, the ALARM relay output and the ALARM LED are
activated. The ALARM output can be used for remote control of the module, e.g. external optical indication. The fuse strip
is located in an enclosure adapted for mounting in RACK standard 19" cabinets.
SPECIFICATIONS
EN
Tel. +48-14-610-19-40, fax: +48-14- 610-19-50, www.pulsar.pl, e-mail:biuro@pulsar.pl
RACK fuse strip
Pulsar
®
Supply voltage
10 V÷56 V DC (-2%/+2%)
Output voltage
U
AUX
= U
IN
(equal to supply voltage)
Current consumption
20mA÷ 50mA @ Uin=10 ÷ 30 V DC
Number of power inputs
1 (DC INPUT terminals) – cable 4 mm
2
max.
The set includes 2.5mm
2
,15cm power cords
Number of power outputs 8 (AUX terminals) –2,5mm
2
max. cable
Protections against:
- a short circuit SCP
- an overload OLP
- 8 x F 2 A glass fuse
- 8 x F 2 A glass fuse
Technical output of failure
ALARM
relay type: 1 A@ 30 V DC/50 V AC
LED indication
- Green LEDs L1 ÷ L8 – outputs status AUX1÷AUX8
- red LED ALARM indicates failure
F1 ÷ F8 fuses
F 2 A
Operating conditions
2nd environmental class, -10°C ÷ 45°C
Dimensions
W=19”, H=2U; 482 x 88 x 74 mm (WxHxD)
Fixing
four-point fixing on the front RACK rails - 4 M6 screws with cage nuts included
Connectors:
- of power input
- of power output
- technical output
Ф0,51÷2,05 (AWG 24-10) 0,2 ÷ 4mm
2
Ф0,51÷2,05 (AWG 24-12) 0,5 ÷ 2,5mm
2
Ф0,51÷2,05 (AWG 24-12) 0,5 ÷ 2,5mm
2
Net/gross weight
2,0/ 2,1kg
Declarations, warranty
CE, 2 year from the production date
Electrical diagram of the relay output.
Electrical diagram.

Summary of content (1 pages)