User Instructions
www.pulsar.pl           RCB12V         RACK POWER 
5 
 Mechanical parameters (Table 3). 
Mounting dimensions 
W=19”, H=2U, D=425 
Dimensions 
W=483, W
1
=435, H=88, D=425, D
1
=15 [+/- 2mm] 
Mounting 
Six-point butt mounting to RACK profiles - a set of 6 M6 screws + cage nuts included 
Net/gross weight 
5,2kg / 5,9kg (without batteries) 
Enclosure 
Steel plate 1,2mm, color RAL 9005 
Connectors 
Battery inputs: 6,3F-2,5 
The BAT output: Φ0,63÷2,50 (AWG 22-10) 0,5-2,5mm
2
The ALARM output: Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2 
Operation parameters (Table 5) 
Environmental class 
II 
Operation temperature 
-10ºC...+40ºC, ensure free air flow around the enclosure 
Storage temperature 
-20ºC...+60ºC 
Relative humidity 
20%...90%, no condensation 
Sinusoidal vibrations during operation: 
Unacceptable 
Surges during operation 
Unacceptable 
Direct insolation 
Unacceptable 
Vibrations and surges during transport 
According to the PN-83/T-42106 standard 
2.  Mounting. 
2.1.  Requirements. 
The enclosure should be mounted by a qualified installer, holding relevant (applicable and required for a 
given country) permits and licenses for low-voltage installations. The device shall be mounted in confined spaces 
(in accordance with the 2nd environmental class) with normal air humidity (RH=90% max. without condensation) 
and the temperature from -10°C to +40°C. In order to meet the requirements of LVD and EMC directives, the rules 
for power supply, enclosures, shielding, and cable routing, depending on application, must be observed. 